5.7.12 Dimension drawing OM-DQ
Dimension drawing
Figure5-27 Dimensions of Option Module OM-DQ
5.7.13 Supplementary fan for option modules, converter in degree of protection
IP20
Overview
The supplementary fan is not mounted in the factory. Under certain requirements, you must
subsequently mount the supplementary fan to cool the converter.
Requirement
The supplementary fan is delivered together with the converter.
The supplementary fan is required if the two subsequent conditions occur:
• Ambient temperature > 50°C
• More than 1 option module is mounted in the converter.
Procedure
Proceed as follows to mount the supplementary fan:
1. Switch o the supply voltage to the converter.
2. Open the front door of the converter.
3. If required, temporarily remove the control cables that prevent the supplementary fan from
being mounted.
Installation
5.7Option modules
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 125