14.11.16.4 Load monitoring for torque
Overview
The "Load monitoring for torque" function assumes that a specic torque is associated with
each speed for pumps and fans.
Description of function
In applications with fans, pumps or compressors with ow characteristic, the torque follows the
speed according to a specic characteristic.
A torque that is too low indicates that the motor and load are no longer mechanically
coupled. A torque that is too high can indicate problems in the mechanical system of the
driven load.
The converter monitors the torque for a lower torque value and an upper torque value using
an envelope curve as a function of speed.
6SHHG>USP@
SVSHHGWKUHVKROG6SHHGWKUHVKROGS
6SHHGWKUHVKROGSSPD[LPXPVSHHG
7RUTXHWKUHVKROGORZHUS
7RUTXHWKUHVKROGXSSHUS
7RUTXHWKUHVKROGORZHUS
7RUTXHWKUHVKROGXSSHUS
7RUTXHWKUHVKROGORZHUS
7RUTXHWKUHVKROGXSSHUS
7RUTXH>1P@
If the torque is in the impermissible range for longer than time p2192, the converter
responds according to the setting p2181.
The monitoring is not active below speed threshold 1 and above speed threshold 3.
Example
In the following examples, a torque that is too high or too low indicates an error in the system:
• For pumps, a torque that is too low can indicate leakage or dry running of the pump.
• For fans, a torque that is too low indicates that the power transmission from the motor to the
load has been interrupted by a broken drive belt.