Table 7-16 Protective conductor at terminal X2 connection (line voltage 3AC 200...240V, IP55)
Converter
6SL4112-..□□-..F0
Protective conductor in terminal X2
-..□□- Frame
size
Rated power
in kW
Conductor cross-
section in mm²
(AWG)
Tightening torque in
Nm (lbfin)
Connection type
05 ... 13 B 0.55 ... 4 1.5 … 6(15 …9) 2 … 3(17.7 …26.6) M4, screw terminal, inside
15 ... 16 C 5.5 … 7.5 1.5 … 16(15 …5) 2 … 3(17.7 …26.6) M4, screw terminal, inside
17 ... 20 D2 11 … 18.5 2.5 … 50 (13...1/0) 5 … 6(44.2 …53.1) M6, stud terminal, inside
21...23 E 22…30 4 … 95 (11...3/0) 8 … 9(70.8 …79.7) M8, stud terminal, inside
7.1.4.5 Connection, converter in degree of protection IP55, 3 AC 380 ... 480 V/500 V
Description
Rigid as well as exible cables can be connected.
Table 7-17 Connection at the converter for the braking resistor (line voltage 3AC 380...415 / 3AC440...500V, IP 55)
Converter
6SL4113-..□□-..F0
Connection at the converter for the braking resistor
-..□□- Frame
size
Rated power
in kW
Conductor cross-
section in mm²
(AWG)
Tightening torque in
Nm (lbfin)
Stripped
length in mm
(in)
Connection type
08…16 B 1.1 … 7.5 2.5 … 6(13 …9) 1.3 (11.5) 12 (0.5) Screw terminal
17 ...18 C 11 ... 15 2.5 … 16(13 …5) 1.3 … 1.4 (11.5 ... 12.4) 12 (0.5) Screw terminal
20...21 D1 18.5...22 2.5 … 16(13 …5) 1.5 … 2.5 (13.3 … 22.1) 10 (0.4) Screw terminal
23...24 D2 30...37 2.5 … 16 (13...5) 1.5 … 2.5 (13.3 ... 22.1) 10 (0.4) Screw terminal
26 ...27 E 45...55 16 … 50 (5...1/0) 8 … 9(70.8 …79.7) 13 (0.5) Screw terminal
Table 7-18 Connection at the converter for the motor (line voltage 3AC 380...415 / 3AC440...500V, IP 55)
Converter
6SL4113-..□□-..F0
Connection at the converter for the motor
-..□□- Frame
size
Rated power
in kW
Conductor cross-
section in mm²
(AWG)
Tightening torque in
Nm (lbfin)
Stripped
length in mm
(in)
Connection type
08…16 B 1.1 … 7.5 2.5 … 6(13 …9) 1.3 (11.5) 12 (0.5) Screw terminal
17 ...18 C 11 ... 15 2.5 … 16(13 …5) 1.3 … 1.4 (11.5 ... 12.4) 12 (0.5) Screw terminal
20...21 D1 18.5...22 6 … 35 (9 …2) 3.8 … 4.5 (33.6 ... 39.8) 18 (0.7) Screw terminal
23...24 D2 30...37 10 … 50(7… 1/0) 5 … 6(44.2 …53.1) 19 (0.7) Screw terminal
26 ...27 E 45...55 35 … 95 (2...3/0) 10 … 12 (88.5 … 106.2) 25 (1) Screw terminal
Connecting
7.1Line system, motor and braking resistor
SINAMICS G220 converter
164 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB