Converter
6SL4112-..□□-..F0
Line supply cable
-..□□- Frame
size
Rated power
in kW
Conductor cross-
section in mm²
(AWG)
Tightening torque in
Nm (lbfin)
Stripped
length in
mm (in)
Connection type
17 ... 20 D2 11 … 18.5 16 … 50(5…1/0) 5.6(49.6) 25 (1) Screw terminal
21...23 E 22…30 35 … 70
1)
(2...2/0)
35 ...95
2)
(2...3/0)
10.2 (90.3) 30 (1.2) Screw terminal
1)
Line supply cable, nely stranded with end sleeve
2)
Line supply cable, solid conductor
Table 7-14 Line supply cable connection with repair switch (line voltage 3AC 200...240V, IP55)
Converter
6SL4112-..□□-..F0
Line supply cable
-..□□- Frame
size
Rated power
in kW
Conductor cross-
section in mm²
(AWG)
Tightening torque in
Nm (lbfin)
Stripped
length in
mm (in)
Connection type
05 ... 13 B 0.55 ... 4 2.5 … 6(13 …9) 2.0...2.5 (17.7...22.1) 9.5 (0.4) Screw terminal
15 ... 16 C 5.5 … 7.5 2.5 … 16 (13...5) 2.0...2.5 (17.7...22.1) 14 (0.6) Screw terminal
17 ... 20 D2 11 … 18.5 10 … 35
1)
(7...2)
10 ...50
2)
(7...1/0)
2.5...3 (22.1...26.6) 14 (0.6) Screw terminal
21...23 E 22…30 35 … 95 (2...3/0) 9.5...10 (84.1...88.5) 15 (0.6) Screw terminal
1)
Line supply cable, nely stranded with end sleeve
2)
Line supply cable, solid conductor
Table 7-15 Protective conductor at terminal X1 connection (line voltage 3AC 200...240V, IP55)
Converter
6SL4112-..□□-..F0
Protective conductor in terminal X1
-..□□- Frame
size
Rated power
in kW
Conductor cross-
section in mm²
(AWG)
Tightening torque in
Nm (lbfin)
Connection type
05 ... 13 B 0.55 ... 4 1.5 … 6(15 …9) 1.5 … 1.7 (13.3...15.0) M5, screw terminal, outside
15 ... 16 C 5.5 … 7.5 1.5 … 16(13 …5) 1.5 … 1.7 (13.3...15.0) M4, screw terminal, outside
17 ... 20 D2 11 … 18.5 2.5 … 50 (13...1/0) 5 … 6(44.2 …53.1) M8, screw terminal, outside
21...23 E 22…30 4 … 95 (11...3/0) 8 … 9(70.8 …79.7) M8, screw terminal, outside
Connecting
7.1Line system, motor and braking resistor
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 163