12.3 Series commissioning using the web server
Overview
For "Series commissioning using the web server" transfer the settings of converter 1 using the
web server to converter 2 or to additional converters.
Procedure
Proceed as follows to perform series commissioning using the web server:
1. Switch on the supply voltage of converter 1.
2. Commission the converter using your operating unit, e.g. a PC.
You can nd more information in Chapter "Commissioning (web server) (Page209)".
3. Save the settings retentively once commissioning has been completed via
.
4. Call the "Backup and restore" menu.
5. Click the "Create backup" button in the "Save drive data to backup le" area.
Optional: Assign a name for the backup le.
The drive data are backed up in the backup le in the download folder of your operating unit.
6. Switch on the supply voltage of converter 2.
7. In the web browser, enter the IP address of the converter 2, e.g. https://169.254.11.22.
You determine the IP address of the converter2, e.g. using the integrated
SINAMICS SDI Standard. You can nd more information in Chapter "Scanning the IP address
(Page317)".
The web server of converter 2 displays page "Basic settings".
8. Make the basic settings for converter 2.
You can nd more information in Chapter "Basic settings (Page214)".
9. In the Security Wizard, select option "Exit the Security Wizard and continue with low security
settings".
10.Call the "Backup and restore" menu.
11.Click the "Click to select le, or drag and drop le here" button to select the backup le.
12.Click on "Restore".
Converter 2 takes the settings from the backup le.
After a restart, the security settings congured in converter 1, e.g. drive password, UMAC
data, become active in converter 2.
Repeat steps 6to12 for all additional converters to which you wish to transfer the settings of
converter 1.
Series commissioning
12.3Series commissioning using the web server
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 299