11.3.2 Simple basic parameterization (oine)
Procedure
The following steps are required for simple basic parameterization:
1. Create or open project with Startdrive.
2. Create the device conguration in Startdrive oine
– Insert the SINAMICS drive into the project and specify it
– Create and specify SINAMICS components
– Make detailed settings for drive and components
– Optional: Congure user administration and make protection settings for the drive
3. Make basic settings oine via the guided quick startup
4. Load project data into the target device.
5. Establish an online connection between Startdrive and the target device
6. Perform optimization
Result:
The motor rotates.
More information
Detailed information can be found in the information system of the TIA Portal in Chapter
"Conguring SINAMICS G220 drives".
11.3.3 Simple basic parameterization (online)
Procedure
The basic parameterization can also be carried out in online mode as an alternative to oine
mode. The results in the following process sequence:
The following steps are required:
1. Create or open project with Startdrive.
2. Create the device conguration in Startdrive oine
– Insert the SINAMICS drive into the project and specify it
– Create and specify SINAMICS components
– Make detailed settings for drive and components
– Optional: Congure user administration and make protection settings for the drive
3. Download project data to the target device
Commissioning (Startdrive)
11.3Device conguration and basic parameterization
SINAMICS G220 converter
284 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB