Technical data
17
17.1 General technical specications
Technical data
Table 17-1 General data of the converter
Property Value
Line voltage 3 AC200V…240V +10%‑20%
3 AC380V…415V +10%‑20%
3 AC440V…500V +10%‑20%
Input frequency 50/60Hz (47…63Hz)
Output voltage 3 AC 0V … line voltage
Output frequency 0…550 Hz
Power factor λ 0.9 typical
Oset factor cos φ 0.98 typical
Pulse frequency 4kHz (factory setting)
The pulse frequency can be set in the range 2…16kHz.
Type of cooling Air cooling using an integrated fan
Degree of pollution 2 according to IEC 61800-5-1
Overvoltage category III according to IEC 61800-5-1
Flicker The icker value of the converter depends on the line supply and the specic
converter application. This means that the icker value can only be measured
when the converter is operational in the installation.