Memory card (SD card)
Memory card content Article number
Firmware V6.2 + license "Safety Integrated Extended Func‐
tions"
6SL4170-1GC00-0AA0-Z F01
Firmware V6.2 + licenses "Motor Control Extended" and "Safety
Integrated Extended Functions"
6SL4170-1GC00-0AA0-Z H01+F01
License "Motor Control Extended" (Download) 6SL5977-0AA00-1DA0
License "Safety Integrated Extended Functions" (download) 6SL5977-0AA00-2HA0
3.6.3 Option module OM-SMT
Overview
Option module OM-SMT extends the functional scope of the converter.
In hazardous areas, option module OM-SMT is suitable for monitoring the temperature of
anexplosion-protected motor of explosion protection types eb, ec and db.
Requirement
For the certied shutdown of the explosion-protected motors according to Directive 2014/34/EU
(ATEX) or Regulation 2016 No. 1107 (UKEX), only suitable explosion-protected motors having
a type A sensor in accordance with IEC 60947-8 are permitted to be used in the corresponding
explosive areas.
The explosive areas must be dened by the operator in accordance with Directive
1999/92/EC. The OM-SMT and the converter must be located outside the explosive areas.
Description
Figure3-4 Option module OM-SMT
Description
3.6Optional components
SINAMICS G220 converter
48 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB