10.3.3 Communication interfaces
Description
The following interfaces are available for accessing the converter:
Interface Information
Service interface X127 Default access to Startdrive and the web server is via service interface X127.
Ethernet interface X127 is intended for commissioning and diagnostics,
which means that it must always be accessible.
Defaults:
IP address: 169.254.11.22
Subnet mask: 255.255.0.0
Data transfer via HTTPS is activated in the factory setting.
Restrictions:
Only local access is allowed.
Only local networking in a closed and locked electrical cabinet is permis‐
sible.
For remote access to the electrical cabinet, you must apply additional In‐
dustrial Cybersecurity measures to prevent misuse through sabotage, data
manipulation by unquali󹪝ed persons and interception of con󹪝dential data.
PROFINET interface
X150
Converters are connected to several components, such as an operating
unit or a higher-level control system, via PROFINET interface X150.
The network at PROFINET interface X150 must be located in a secure pro‐
tection zone. Access to cables and open connections must be implemen‐
ted in a protected fashion, such as in a control cabinet.
The IP addresses of the service interface X127 and the PROFINET interface
X150 must not be in the same subnet.
Con󹪝gured IP addresses are stored in SINAMICS SDI Standard:
"Support" menu > "Scan IP Address".
More information
More information about the supported protocols is available on the Internet:
Industrial Cybersecurity Con󹪝guration Manual (https://
support.industry.siemens.com/cs/ww/en/view/109810578)
Commissioning (web server)
10.3Fundamentals
SINAMICS G220 converter
212 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB