16.4 Firmware update of option module OM-IIoT
Requirement
The following preconditions apply when updating the rmware of option module OM-IIoT:
• You have downloaded a le with the rmware update from the Internet.
• The network settings of the OM-IIoT have been completely congured using Startdrive or the
web server:
– IP address
– Subnet mask
– Gateway
• A UMAC account for a user with one of the following authorizations has been created for the
converter using Startdrive or the web server:
– Drive Administrator
– Drive Safety Engineer
– Drive Engineer and Service
As example, the following data are used in the procedure:
• Login name for Startdrive or web server = xx0
• Authorization for Startdrive or web server = Drive Administrator
• IP address of the OM-IIoT = 169.254.1.42
• PC with Windows operating system and the storage location of the le for the rmware
update D:\IIOT\IIoT_upgrade\
Procedure
Proceed as follows to update the rmware of option module OM-IIoT:
1. Save the le for the rmware update with name
SINAMICS_IIoT_Module_rmware_Vxx_xx_xxx_xxx.zip in any folder on your PC.
2. Connect your PC to network connection X128 of the OM-IIoT via a network cable.