16.4 Firmware update of option module OM-IIoT
Requirement
The following preconditions apply when updating the 󹪝rmware of option module OM-IIoT:
You have downloaded a 󹪝le with the 󹪝rmware update from the Internet.
The network settings of the OM-IIoT have been completely con󹪝gured using Startdrive or the
web server:
IP address
Subnet mask
Gateway
A UMAC account for a user with one of the following authorizations has been created for the
converter using Startdrive or the web server:
Drive Administrator
Drive Safety Engineer
Drive Engineer and Service
As example, the following data are used in the procedure:
Login name for Startdrive or web server = xx0
Authorization for Startdrive or web server = Drive Administrator
IP address of the OM-IIoT = 169.254.1.42
PC with Windows operating system and the storage location of the 󹪝le for the 󹪝rmware
update D:\IIOT\IIoT_upgrade\
Procedure
Proceed as follows to update the 󹪝rmware of option module OM-IIoT:
1. Save the 󹪝le for the 󹪝rmware update with name
SINAMICS_IIoT_Module_󹪝rmware_Vxx_xx_xxx_xxx.zip in any folder on your PC.
2. Connect your PC to network connection X128 of the OM-IIoT via a network cable.
Corrective maintenance
16.4Firmware update of option module OM-IIoT
SINAMICS G220 converter
770 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB