14.11.16.11 Motor protection with temperature switch
Overview
To protect the motor against overtemperature, the converter can evaluate a temperature switch,
such as a bimetal switch.
Description of function
The converter interprets a resistance ≥100Ω as an open bimetallic switch and responds
according to the setting for p0610.
Parameters
The following list contains the parameters of the "Motor protection with temperature switch"
function.
Number Name Unit
p0335[0...n] Motor cooling type
p0601[0...n] Motor temperature sensor type
p0610[0...n] Motor overtemperature response
14.11.16.12 Motor protection with temperature sensor PTC
Overview
To protect the motor against overtemperature, the converter can evaluate a PTC sensor.
Description of function
The converter interprets the resistance as follows:
• Resistance>1650Ω: Overtemperature
The converter responds according to the setting for p0610.
• Resistance<20Ω: Short-circuit
The converter responds with alarm A07015.
If the alarm is present for longer than 100 milliseconds, the converter shuts down with fault
F07016.
Parameters
The following list contains the parameters of the "Motor protection with temperature sensor
PTC" function.
Number Name Unit
p0335[0...n] Motor cooling type
p0601[0...n] Motor temperature sensor type
Functions