Loading...
Attrib‐
ute ID
Service
1)
Type Name Value/explanation
4 get UNIT16 Physical Link Path Size (in WORDs); 󹪝xed val‐
ue: 2 hex
UNIT8 Path (20 hex, F6 hex, 24 hex, 05
hex, where 5 hex is the number
of instances of F6 hex: 4 physical
ports plus an internal port).
5 get, set STRING Interface Con󹪝guration r61000 Name of Station
UNIT32 r61001 IP address
6 get, set UNIT16 Host Name Host Name Length
STRING
10 get, set UNIT8 Select ACD local OM 󹪞ash:
0: Disabled,
1: Enabled
11 get, set UNIT8 Last Con󹪞ict Detected local OM 󹪞ash ACD Activity
UNIT8 local OM 󹪞ash Remote MAC
UNIT8 local OM 󹪞ash ARP PDU
1)
Supported services: Get Attribute all, get attribute single, set attribute single
14.6.4.4 "Ethernet link object" class
Overview
The "Ethernet link object" enables communication diagnostics.
Description of function
The "Ethernet link object" has object class F6hex.
Table 14-55 Class attributes
Attrib‐
ute ID
Service
1)
Type Name
1 get UINT16 Revision
2 get UINT16 Maximum instance
3 get UINT16 Number of instances
1)
Supported services: Get attribute all, get attribute single
Functions
14.6Ethernet/IP communication
SINAMICS G220 converter
406 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB