Converter Semiconductor fuses Minimal electrical cabi‐
net envelope dimen‐
sions for converters
with degree of protec‐
tion UL open type
Rated power /
kW
Article number Article number Rated current / A SCCR / kA @
240V
22 6SL4112-...21-..F0 3NE1022-0 125 100 0.384m³ 13.56ft³
30 6SL4112-...23-..F0 3NE1224-0 160 100 0.384m³ 13.56ft³
More information
Additional overcurrent protective devices are available on the Internet:
Protective devices for SINAMICS G220 (https://support.industry.siemens.com/cs/ww/en/view/
109823568)
7.1.7.3 Overcurrent protection, 3 AC 380 V … 415 V / 3 AC 440 V … 500 V
Description
Table 7-25 Standard fuses IEC standard, 3 AC 380 V … 415 V / 3 AC 440 V … 500 V
Converter Standard fuse Minimal electrical cabi‐
net envelope dimen‐
sions for converters
with degree of protec‐
tion IP20
Rated power /
kW
Article number Article number Rated current / A ICC / kA @
240V
1.1 6SL4113-...08-..F0 3NA3801 6 100 0.192m³ 6.78ft³
1.5 6SL4113-...10-..F0 3NA3803 10 100 0.192m³ 6.78ft³
2.2 6SL4113-...11-..F0 3NA3803 10 100 0.192m³ 6.78ft³
3 6SL4113-...12-..F0 3NA3805 16 100 0.192m³ 6.78ft³
4 6SL4113-...13-..F0 3NA3805 16 100 0.192m³ 6.78ft³
5.5 6SL4113-...15-..F0 3NA3807 20 100 0.24m³ 8.48ft³
7.5 6SL4113-...16-..F0 3NA3812 32 100 0.24m³ 8.48ft³
11 6SL4113-...17-..F0 3NA3817 40 100 0.12m³ 4.24ft³
15 6SL4113-...18-..F0 3NA3820 50 100 0.12m³ 4.24ft³
18.5 6SL4113-...20-..F0 3NA3822 63 100 0.288m³ 10.71ft³
22 6SL4113-...21-..F0 3NA3824 80 100 0.288m³ 10.71ft³
30 6SL4113-...23-..F0 3NA3830 100 100 0.36m³ 12.71ft³
37 6SL4113-...24-..F0 3NA3830 100 100 0.36m³ 12.71ft³
45 6SL4113-...26-..F0 3NA3832 125 100 0.384m³ 13.56ft³
55 6SL4113-...27-..F0 3NA3836 160 100 0.384m³ 13.56ft³
Connecting
7.1Line system, motor and braking resistor
SINAMICS G220 converter
172 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB