14.11.8 Armature short-circuit braking
Overview
Armature short-circuit braking brakes the load. During braking, armature short-circuit braking
converts the kinetic energy of the load in the motor into heat.
Requirement
Requirements:
The armature short-circuit braking function is possible only for permanently excited
synchronous motors.
Motor rated short-circuit current p0320 < Maximum motor current p0323
Additional requirement for internal armature short-circuit braking:
Power unit maximum current r0209[0] ≥ 1.8·rated short-circuit current r0331
WARNING
Motor acceleration by pulling load
A pulling load may accelerate the motor signi󹪝cantly even if armature short-circuit braking is
active. An unexpectedly high speed can damage the machine or result in death or serious injury.
If there is a pulling load, use a mechanical brake in addition to the armature short-circuit
braking.
Description of function
A "1" signal of the binary signal sink p1230 activates the "Armature short-circuit braking"
function.
A "0" signal of the binary signal sink p1230 deactivates the "Armature short-circuit braking"
function.
The "Armature short-circuit braking" function brie󹪞y closes the stator windings of the
synchronous motor. If the synchronous motor is rotating, a current 󹪞ows that brakes the
motor.
Functions
14.11Drive functions
SINAMICS G220 converter
596 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB