17.9 Power loss
17.9.1 3 AC 200 ... 240 V, degree of protection IP20
Technical data
Table 17-16 Absolute power loss in W at operating point (90/100)
1)
Article number Rated power IEC NEC
6SL4112-...☐☐-..F0 @ 230V, 50Hz @ 240V, 60Hz
05 0.55kW 66.9 58.1
06 0.75kW 78.6 71.5
08 1.1kW 107 98.6
10 1.5kW 144 112
11 2.2kW 191 166
12 3kW 202 174
13 4kW 277 213
15 5.5kW 373 296
16 7.5kW 498 392
17 11kW 566 511
18 15kW 842 694
20 18.5kW 1061 935
21 22kW 1154 1002
23 30kW 1527 1391
1)
The operating point (90/100) means: relative motor stator frequency 90%, relative torque current 100%
Power loss was measured at a pulse frequency of 4kHz and with space-vector modulation.