4.7 Operation on a TN system
Overview
The converter is suitable for connection to a TN system.
Requirement
The following applies to the connection of converters to a TN system:
Converter with integrated or external line 󹪝lter:
Operation on TN systems with grounded neutral point is permissible
Operation on TN systems with grounded line conductor not permissible
Converter without line 󹪝lter:
Operation on all TN systems permissible
Description
The TN system transfers the PE protective conductor to the installed electrical installation using
a conductor.
Generally, the neutral point is grounded in a TN system. There are versions of a TN system
with grounded line conductor, e.g. with grounded L1.
The TN system can transfer the neutral conductor N and the PE protective conductor either
separately or combined.
Figure4-1 TN system
Application planning
4.7Operation on a TN system
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 71