7.1.4.4 Connection, converter in degree of protection IP55, 3 AC 200 ... 240 V
Description
Rigid as well as exible cables can be connected.
Table 7-11 Connection at the converter for the braking resistor (line voltage 3AC 200...240V, IP55)
Converter
6SL4112-..□□-..F0
Connection at the converter for the braking resistor
-..□□-
Frame
size
Rated pow‐
er in kW
Conductor cross-
section in mm²
(AWG)
Tightening torque in
Nm (lbfin)
Stripped
length in
mm (in)
Connection type
05 ... 13 B 0.55 ... 4 2.5 … 6(13 …19) 1.3 (11.5) 12 (0.5) Screw terminal
15 ... 16 C 5.5 … 7.5 2.5 … 16(13 …5) 1.3 … 1.4 (11.5...12.4) 12 (0.5) Screw terminal
17 ... 20 D2 11 … 18.5 2.5 … 16(13 …5) 1.5 … 2.5 (13.3...22.1) 10 (0.4) Screw terminal
21...23 E 22…30 16 … 50(5… 1/0) 8 … 9(70.8 …79.7) 13 (0.5) Screw terminal
Table 7-12 Connection at the converter for the motor (line voltage 3AC 200...240V, IP55)
Converter
6SL4112-..□□-..F0
Connection at the converter for the motor
-..□□-
Frame
size
Rated pow‐
er in kW
Conductor cross-
section in mm²
(AWG)
Tightening torque in
Nm (lbfin)
Stripped
length in
mm (in)
Connection type
05 ... 13 B 0.55 ... 4 2.5 … 6(13 …9) 1.3 (11.5) 12 (0.5) Screw terminal
15 ... 16 C 5.5 … 7.5 2.5 … 16(13 …5) 1.3 … 1.4 (1.3...12.4) 12 (0.5) Screw terminal
17 ... 20 D2 11 … 18.5 10 … 50 (5...1/0) 5 … 6(44.2 …53.1) 19 (0.7) Screw terminal
21...23 E 22…30 35 … 95 (2...3/0) 10 … 12(88.5 …106.2) 25 (1) Screw terminal
Table 7-13 Line supply cable connection without repair switch (line voltage 3AC200...240V, IP 55)
Converter
6SL4112-..□□-..F0
Line supply cable
-..□□- Frame
size
Rated power
in kW
Conductor cross-
section in mm²
(AWG)
Tightening torque in
Nm (lbfin)
Stripped
length in
mm (in)
Connection type
05 ... 13 B 0.55 ... 4 1.5 … 6(15 …9) 1.2 (10.6) 12 (0.5) Screw terminal
15 ... 16 C 5.5 … 7.5 2.5 … 16(13 …5) 2.5 … 3.4 (22.1...30.1) 14 (0.6) Screw terminal
Connecting
7.1Line system, motor and braking resistor
SINAMICS G220 converter
162 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB