17.13.4 Climatic conditions
Technical data
Table 17-28 Resistance to climatic conditions
Usage phase Classi󹪝cation Description
Storage Class 1K4 according to
IEC60721-3-1:1997
In the transport packaging
Temperature -25…+55°C
Humidity 5...95%
Storage altitude ≤ 4000m
Condensation, splash water, icing, salt spray not permissible
Transport Class 2K4 according to
IEC60721-3-2:1997
In the transport packaging
Temperature -40…+70°C
Humidity 5...95%
Operation Class 3K3 in accordance with IEC
60721-3-3 Ed. 2.2: 2002
With increased ruggedness with respect to relative humidity
Temperature -20…+60°C for IP20 degree of protection
Temperature -20…+50°C for IP55 degree of protection
Relative humidity 5 ... 95 % no condensation (better than Class
3K3)
Ice formation, condensation, dripping water, spraying water,
splashing water and water jets are not permitted.
Technical data
17.13Option modules
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 827

Table of Contents