The following cables must be shielded to comply with EMC regulations:
In the electrical cabinet:
Cable between the converter and an external line 󹪝lter
Cable between the converter and the motor
Cable between the converter and the braking resistor
Fieldbus cable
Cables for analog inputs and analog outputs
DRIVE-CLiQ cable to the encoder
Cable to the temperature sensor
Outside the electrical cabinet, all cables with the exception of the line supply cable
4.14.8 Maximum permissible signal cable lengths, converter in degree of
protection IP20
Technical data
Table 4-5 Maximum permissible signal cable lengths, IP20
Connection at the converter Cable length
24 V supply (terminals X124:1…
4)
We recommend using a Schurter FPBB 3-103-715 line 󹪝lter in the
following cases.
When operating with an OM-DQ option module with an encoder,
type 6FX
If conducted disturbances occur on the 24V cable
A surge protection device is additionally required for connection ca‐
bles longer than 30 m.
We recommend surge protection device DCO SD2 E 48, Order No.
917989.
Digital input
Failsafe digital input
The maximum permissible connecting cable length is 1000m.
A surge protection device is required for connection cables longer
than 30 m.
We recommend surge protection device DCO SD2 ME 24, Order No.
DEHN 917921.
Digital output DO0 The maximum permissible connecting cable length is 1000m.
A surge protection device is required for connection cables longer
than 30 m.
We recommend surge protection device DCO SD2 ME 24, Order No.
DEHN 917921.
Application planning
4.14EMC-compliant installation
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 87