The following cables must be shielded to comply with EMC regulations:
• In the electrical cabinet:
– Cable between the converter and an external line lter
– Cable between the converter and the motor
– Cable between the converter and the braking resistor
– Fieldbus cable
– Cables for analog inputs and analog outputs
– DRIVE-CLiQ cable to the encoder
– Cable to the temperature sensor
• Outside the electrical cabinet, all cables with the exception of the line supply cable
4.14.8 Maximum permissible signal cable lengths, converter in degree of
protection IP20
Technical data
Table 4-5 Maximum permissible signal cable lengths, IP20
Connection at the converter Cable length
24 V supply (terminals X124:1…
4)
We recommend using a Schurter FPBB 3-103-715 line lter in the
following cases.
• When operating with an OM-DQ option module with an encoder,
type 6FX
• If conducted disturbances occur on the 24V cable
A surge protection device is additionally required for connection ca‐
bles longer than 30 m.
We recommend surge protection device DCO SD2 E 48, Order No.
917989.
Digital input
Failsafe digital input
The maximum permissible connecting cable length is 1000m.
A surge protection device is required for connection cables longer
than 30 m.
We recommend surge protection device DCO SD2 ME 24, Order No.
DEHN 917921.
Digital output DO0 The maximum permissible connecting cable length is 1000m.
A surge protection device is required for connection cables longer
than 30 m.
We recommend surge protection device DCO SD2 ME 24, Order No.
DEHN 917921.
Application planning
4.14EMC-compliant installation
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 87