4.8 Operation on a TT system
Overview
The converter is suitable for connection to a TT system.
Requirement
The following applies to the connection of converters to a TT system:
Operation in installations according to IEC and UL
For installations according to IEC, operation on TT systems is permissible.
For installations according to UL, operation on TT systems is not permissible.
Converter with integrated or external line 󹪝lter
Operation on TT systems with grounded neutral point is permissible
Operation on TT systems without grounded neutral point is not permissible
Converter without line 󹪝lter
Operation on all TT systems permissible
Description
In a TT system, the PE protective conductor of the transformer and the installed system are
independent of one another.
There are TT systems with and without transfer of the neutral conductor N.
7UDQVIRUPHURU
JHQHUDWRU
7RWKHV\VWHP
([DPSOH7UDQVIHURI1JURXQGHGQHXWUDO
SRLQW
/
/
/
1
3(
Figure4-2 Example: Transfer of the neutral conductor, grounded neutral point
Application planning
4.8Operation on a TT system
SINAMICS G220 converter
72 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB