Siemens SINAMICS G220 - Setting the Energy-Saving Mode

Siemens SINAMICS G220
834 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The converter exits hibernation mode2 under the following conditions:
The higher-level control goes into stop.
The bus connection to the higher-level control is interrupted.
Parameters
The following list contains the parameters of the "Energy-saving mode" function.
Number Name Unit
r5600 PROFIenergy energy-saving mode ID
p5611.0...2 PROFIenergy energy-saving properties general
r5613.0...1 PROFIenergy energy saving active/inactive
14.4.10.3 Setting the energy-saving mode
Overview
Various setting modes are available for the energy-saving mode.
Settings
Adjust the energy-saving mode using the information in the following table:
Table 14-14 Energy-saving mode settings
Settings Parameters Result
Inhibiting PROFIenergy p5611.0=1 They block the reaction of the converter to PROFIenergy control com‐
mands.
In this case, the converter rejects the "Start_Pause" command with 50
hex (no appropriate pause mode).
Transition to energy-saving
mode
p5611.2=0 With p5611.2=0, you enable the transition to energy-saving mode
from operating state S1 (switching on inhibited) or S2 (ready to switch
on).
With p5611.2=1 With p5611.2=1, you enable the transition to energy-saving mode
from operating states S3 (ready for operation) and S4 (operation).
Additional settings:
p5611.1=1 With the transition to energy-saving mode, the converter triggers an
OFF1 command and enters the switching on inhibited state (S1).
p5611.1=0 You use p5614 to interconnect a signal source that you use to switch
o󹪜 the converter and place it in switching on inhibited state (S1).
Functions
14.4PROFINET communication
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 379