EasyManua.ls Logo

Siemens SINAMICS G220 - Retentively Saving Changes

Siemens SINAMICS G220
834 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11.2.6 Retentively saving changes
Overview
You have created and fully con󹪝gured a drive in the project and you wish to save your settings
in the converter.
Parameter assignments of your drive are always volatile and are lost when the drive is
switched o󹪜. Information is subsequently provided as to how you can retentively save online
data or o󹪠ine data.
Requirement
A project has been created.
For activated user management (UMAC):
The function rights for editing drive data are activated for your user account.
Details on this topic are provided in the Con󹪝guration Manual SINAMICS Industrial Security
(
https://support.industry.siemens.com/cs/ww/en/view/109810578) in Chapter "Security
settings in Startdrive".
Retentively saving online data
You are connected online with the drive; save your con󹪝guration as follows:
1. In the function view of the active Startdrive project, click on icon (retentively save data
of the complete device).
OR
2. In the project tree of your drive device, double-click on "Online & Diagnostics".
In the secondary navigation select menu "Functions > Backup/Restore".
In the "Retentively save RAM data" area, click "Save".
The system checks whether a memory card is available. If an appropriate memory card is
detected, then the parameter values are retentively saved to the memory card.
Retentively saving o󹪠ine data
When retentively saving data, it is important that the settings made are not only saved on your
operating unit in the Startdrive project, but also permanently saved on the drive memory card
(also known as "save retentively" or "RAM to ROM"). An online connection must be established
to the drive for this purpose.
1. Establish an online connection to your drive.
2. Load the project data into your drive.
3. Click the icon in the function view of the active Startdrive project.
The current project settings are stored retentively on the memory card of the drive.
Commissioning (Startdrive)
11.2Basics
SINAMICS G220 converter
280 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB

Table of Contents

Related product manuals