4.14.5 EMC-compliant shield support
Requirement
Use shielded cables with 󹪝nely stranded braided shields.
Description
Requirements placed on EMC-compliant shield supports:
The shield is never interrupted.
Connect the shields at both ends of the cable as close as possible to the cable connection
locations through a large surface area.
Metal or metalized plug connectors are used to connect shielded data cables.
Example
Examples of shield supports on a shield plate and a mounting plate are shown in the following
diagram.
3FNPWFUIFJOTVMBUJPOBOE
FYQPTFUIFDBCMFTIJFME
.PVOUJOHQMBUF
4IJFMEQMBUF
4IJFMETVQQPSU
;JH[BHUBQF;JH[BHUBQF
)PTFDMBNQ)PTFDMBNQ
Figure4-6 Examples of EMC-compliant shield supports
Application planning
4.14EMC-compliant installation
SINAMICS G220 converter
84 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB