The Safety Integrated Functions correspond to the functions according toIEC 61800‑5‑2 and
IEC61800‑5‑3.
The individual Safety Integrated components have the following certications:
Table 14-88 Certications for the converter Safety Integrated component
Converter SIL PL Category
Control via PROFIsafe SIL 3 PL e Category 4
Control via F-DI SIL 3 PL e Category 3 or 4
1)
Stop functions STO, SS1 SIL 3 PL e Category 4
Safe Motor Temperature (SMT) SIL 2 PL d Category 3
Motion monitoring functions SLS, SDI, SSM SIL 3 PL e Category 3
1)
Depending on the parameterized self-test of the fail-safe digital inputs
14.12.2 PFH values
Description
The probability of failure for Safety Integrated Functions must be specied in the form of a PFH
value (probability of failure per hour) according to IEC 61800-5-2, IEC62061 andEN
ISO 13849-1. The PFH value of a Safety Integrated Function depends on the safety concept of the
converter and its hardware conguration, as well as on the PFH values of other components used
for this Safety Integrated Function.
More information
The PFH values can be found under: PFH values (https://
support.industry.siemens.com/cs/ww/en/view/76254308)
You can map the PFH values of all Safety Integrated components
from Siemens using the "Safety evaluation" function in the TIA selection
tool: Safety evaluation (https://new.siemens.com/global/en/products/automation/topic-areas/
safety-integrated/factory-automation/support/tia-safety-evaluation-tool.html)
14.12.3 EMERGENCY OFF and EMERGENCY STOP
Overview
In plants, systems and machines a distinction must be made between EMERGENCY OFF and
EMERGENCY STOP.
The Safe Torque O (STO) and Safe Stop 1 (SS1) Safety Integrated Functions are suitable for
implementing an EMERGENCY STOP, but are not suitable for implementing an EMERGENCY
OFF.
Functions
14.12Safety Integrated
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 657