The sampling time p4448 denes the time intervals of the signal values.
Table 14-62 Sampling time
Value of p4448 Sampling time
< 375µs 250µs
375µs … < 750µs 500µs
750µs … < 1.5ms 1ms
1.5ms … < 3ms 2ms
≥ 3ms 4ms
Parameters
The following list contains the parameters for the "Communication with edge device" function.
Number Name Unit
c4441[0...15] IIOT signal sinks
r4446.0...17 IIOT status
p4447.0 IIOT conguration
p4448 IIOT sampling time cyclic signal transfer [µs]
14.7.2 Congure communication with the converter in the edge device
Overview
You must congure communication with the option module OM-IIoT in the edge device.
Requirement
You have congured communication with the edge device in the converter using a
commissioning tool.
The procedure includes as example the "Drive System Framework" app that runs in the edge
device.
Functions
14.7Communication with edge device
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 415