17.6 Permissible motor cable length as a function of the pulse
frequency
Technical data
Table 17-14 Maximum permissible motor cable length as a function of the pulse frequency, 380V …
415V and 200V … 240V
Frame size Pulse frequency
4kHz 8kHz 12kHz 16kHz
FSA 200m 200m 50m 25m
FSB 200m 200m 150m 50m
FSC 200m 200m 200m 75m
Table 17-15 Maximum permissible motor cable length as a function of the pulse frequency, 440V …
500V
Frame size Pulse frequency
4kHz 8kHz 12kHz 16kHz
FSA 200m 100m 25m 5m
FSB 200m 200m 100m 25m
FSC 200m 200m 100m 50m
Technical data
17.6Permissible motor cable length as a function of the pulse frequency
SINAMICS G220 converter