14.4.10.5 Status queries in energy-saving mode
Overview
The converter returns information about the settings and status of energy saving mode to the
higher-level controller via status queries.
Description of function
The following table shows the available status queries.
Table 14-16 Status queries energy-saving mode
Command Explanation
List_Energy_Saving_Modes Returns all supported energy-saving modes
Get_Mode Provides information about the selected energy-saving mode
PEM_Status Returns the current PROFIenergy status
PEM_Status_with_CTTO Returns the current PROFIenergy status together with the regular
transition time to the operating state
PE_ldentify Returns the supported PROFIenergy commands
Query_Version Returns the implemented PROFIenergy prole
Query_Attributes Returns the attributes of the implemented PROFIenergy prole
Get_Measurement_List Returns the measured value IDs that can be accessed using the
"Get_Measurement_Values" command
Get_Measure‐
ment_List_with_object_number
Returns the measured value IDs and the associated object number
that can be accessed using the "Get_Measurement_Values_with_ob‐
ject_number" command
Get_Measurement_Values Returns the measured values requested via the measured value ID
Get_Measurement_Val‐
ues_with_object_number
Returns the measured values requested via the measured value ID and
the object number. The object number corresponds to the drive ob‐
ject ID.
Table 14-17 Measured values
PROFIenergy SINAMICS source parameters Value
range
Measured value Accuracy Unit
ID Name Do‐
main
Class Number Name
34 Active power 1 12 W r0032 Active power smoothed r2004
166 Power factor 1 12 1 r0038 Smoothed power factor 0...1
200 Active energy im‐
port
2 11 Wh r0039[1] Energy accepted -
Functions
14.4PROFINET communication
SINAMICS G220 converter
382 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB