- 2382 -
1
PROFIenergy
States
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
PROFIenergy
POWER OFF
POWER ON
<1>
&
Start_Pause
&
1 = Trans to energy-saving mode from
PROFIdrive state S3/4 poss
p5611.2 (0)
1 = Inhibit PROFIenergy control commands
p5611.0 (0)
1 = Drive initiates OFF1
when transitioning to
energy-saving mode
p5611.1 (0)
S1: Switching on
inhibited
S2: Ready for
switching on
S3: Ready for
operation
S4: Operation
OFF1
r5613
r5613.0
1 = PROFIenergy active
PROFIenergy energy-
saving mode ID
r5600
r5613
r5613.1
1 = PROFIenergy inactive
Drive at standstill
Connection termination
Energy-saving mode
active
PROFIenergy
Operation
PROFIenergy
Ready for operation
PROFIenergy
Energy-saving mode
2
A08800
PROFIenergy
<2>
1
&
Start_Pause
≥1
End_Pause
CPU STOP
1 = Inhibit PROFIenergy
control commands
p5611.0 (0)
StatesPROFIdrive StatesPROFIenergy
<2>
<1>
Diagnostic alarms to the CPU inhibited.
Excerpt from: Basic state machine of a PROFIdrive drive axis (source: PROFIBUS Nutzerorganisation (PNO)).
≥1
Figure14-29 2382 - States
Functions
14.4PROFINET communication
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 383