EasyManua.ls Logo

Siemens SINAMICS G220 - 14.11.16.10 Motor Protection with Temperature Sensor Pt1000

Siemens SINAMICS G220
834 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
p0601[0...n] Motor temperature sensor type
p0604[0...n] Mot_temp_mod 2/sensor: alarm threshold [°C]
p0605[0...n] Mot_temp_mod 1/2 sensor threshold and temperature value [°C]
p0610[0...n] Motor overtemperature response
p0624[0...n] Motor temperature o󹪜set Pt100 [K]
14.11.16.10 Motor protection with temperature sensor Pt1000
Overview
To protect the motor against overtemperature, the converter can evaluate the Pt1000 sensor.
Description of function
With a Pt1000 sensor, the converter evaluates the motor temperature in the range -48°C ...
+248°C.
You set the temperature for the alarm and fault thresholds with parameters p0604 and
p0605, respectively.
Alarm overtemperature (A07910)
Motor temperature>p0604 and p0610=0
Overtemperature fault (F07011)
The converter responds with a fault in the following cases:
Motor temperature> p0605
Motor temperature>p0604 and p0610>0
Sensor monitoring
Wire break:
After 100milliseconds, the converter transitions into fault state F07016.
Short-circuit:
After 100milliseconds, the converter transitions into fault state F07016.
Parameters
The following list contains the parameters of the "Motor protection with temperature sensor
Pt1000" function.
Number Name Unit
p0335[0...n] Motor cooling type
p0601[0...n] Motor temperature sensor type
p0604[0...n] Mot_temp_mod 2/sensor: alarm threshold [°C]
p0605[0...n] Mot_temp_mod 1/2 sensor threshold and temperature value [°C]
p0610[0...n] Motor overtemperature response
Functions
14.11Drive functions
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 629

Table of Contents

Related product manuals