4.13.5 Current harmonics
Technical data
When operated with rated power, the converter generates the following typical current
harmonics:
Table 4-4 Components of the harmonic I5 ... I15 relative to the fundamental current
R
SC
I5 I7 I11 I13 I17 I19 I23 I25 THC
120 34.5% 17.6% 8% 5.2% 4.5% 3.3% 3% 2.4% 40.3%
33 30.7% 11.6% 7.3% 5.1% 3.5% 2.5% 2% 1.7% 33.2%
R
SC
= Relative Short-Circuit power: Ratio between short-circuit power at the mains connection point to the
fundamental frequency apparent power Sof the connected converters
THC = Total Harmonic Current: Sum of all harmonic currents
4.13.6 EMC limit values in South Korea
Description
The EMC limit values to be observed for Korea correspond to the limit values of the EMC
product standard for variable-speed electric drives EN61800-3 of categoryC2 or the limit
value classA, Group1 to KN11.
By implementing appropriate additional measures, the limit values according to categoryC2
or limit value classA, Group1, are observed.
Additional measures, such as the use of an additional RFI suppression lter (EMC lter), may
be necessary.
In addition, measures for EMC-compliant conguration of the plant or system are described
in detail in this manual.
The nal statement on compliance with the applicable standard is given by the respective
label attached to the individual device.