6.1.7 Minimum clearances, converter in degree of protection IP55
Dimension drawing
.JOJNVNDMFBSBODF
BUUIFUPQ
3FDPNNFOEFENJOJNVN
DMFBSBODFBUUIFGSPOU
.JOJNVNDMFBSBODF
BUUIFCPUUPN
Figure6-6 IP55 minimum clearances
Table 6-7 Minimum clearances
Unit FSB FSC FSD1 FSD2 FSE
Minimum ventila‐
tion clearance
above
mm 103 115 143 163 195
Minimum ventila‐
tion clearance be‐
low
mm 103 115 143 163 195
Recommended min‐
imum clearance at
the front
mm 40 40 40 45 75
Mounting
6.1Converter
SINAMICS G220 converter
138 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB