10.4 Getting Started
10.4.1 Calling the web server
Overview
The converter is commissioned via the user interface of the web server.
Requirement
Requirements:
You have connected the converter to the operating unit via the service interface X127.
Guest access to the web server is active.
If guest access is not permitted, you must log in with your user name and password when
calling the web server.
Procedure
To access the web server via service interface X127, enter the IP address of the converter into the
web browser, e.g. https://169.254.11.22.
If you do not know the IP address, then at the SINAMICS SDI standard navigate to menu
"Support" > "Scan IP Address".
More information
To access the integrated web server, you must assign PROFINET interface X150 a valid IP address
via the control system. The IP addresses of X127 and X150 must be di󹪜erent.
10.4.2 Settings for brand-new converters
Overview
The basis settings are required before performing 󹪝rst commissioning for a brand-new converter.
Requirement
The operating unit is connected to the converter via service interface X127.
The web server can be accessed via service interface X127 using the con󹪝gured IP address
(default: 169.254.11.22).
Commissioning (web server)
10.4Getting Started
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 213