Parameters
The following list contains the parameters of the "U/f control with Standard Drive Control"
function.
Number Name Unit
r0025 Output voltage smoothed [Vrms]
r0066 Output frequency [Hz]
r0071 Maximum output voltage [Vrms]
p0304[0...n] Rated motor voltage [Vrms]
p0310[0...n] Rated motor frequency [Hz]
p0501[0...n] Technological application (Standard Drive Control)
14.10.2.2 Setting of technological application in Standard Drive Control
Overview
The selected technological application optimizes the calculation of the open-loop and closed-
loop control parameters in Standard Drive Control operating mode.
Description of function
The following settings are available to select for open-loop speed control with parameter p0501.
Table 14-70 Setting of technological application in Standard Drive Control
0 Constant load (linear characteristic)
Setting for all applications without speed-dependent
load characteristic
High load torque even at low speeds
1 Speed-dependent load (parabolic charac‐
teristic)
Setting, e.g. for parabolic load characteristics for
pumps, fans
Only small load torques at low speeds
Full load is reached at the rated operating point
If high load surges in the range of low and medium
speeds cannot be ruled out, we recommend setting
p501=0.
14.10.2.3 Optimized motor startup in Standard Drive Control operating mode
Overview
The startup behavior of the motor can be improved by increasing the current at low speeds.
Functions
14.10Closed-loop drive control
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 467