Parameters
The following list contains the parameters of the "U/f control with Standard Drive Control"
function.
Number Name Unit
r0025 Output voltage smoothed [Vrms]
r0066 Output frequency [Hz]
r0071 Maximum output voltage [Vrms]
p0304[0...n] Rated motor voltage [Vrms]
p0310[0...n] Rated motor frequency [Hz]
p0501[0...n] Technological application (Standard Drive Control)
14.10.2.2 Setting of technological application in Standard Drive Control
Overview
The selected technological application optimizes the calculation of the open-loop and closed-
loop control parameters in Standard Drive Control operating mode.
Description of function
The following settings are available to select for open-loop speed control with parameter p0501.
Table 14-70 Setting of technological application in Standard Drive Control
0 Constant load (linear characteristic)
• Setting for all applications without speed-dependent
load characteristic
• High load torque even at low speeds
1 Speed-dependent load (parabolic charac‐
teristic)
• Setting, e.g. for parabolic load characteristics for
pumps, fans
• Only small load torques at low speeds
• Full load is reached at the rated operating point
• If high load surges in the range of low and medium
speeds cannot be ruled out, we recommend setting
p501=0.
14.10.2.3 Optimized motor startup in Standard Drive Control operating mode
Overview
The startup behavior of the motor can be improved by increasing the current at low speeds.
Functions
14.10Closed-loop drive control
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 467