Requirement
Standard Drive Control works only with an induction motor.
Description of function
8IFKDUDFWHUL
VWLF
6OLSFRPSHQVD
WLRQ
9ROWDJHERRVW
QൺI
6SHHGVHWSRLQW
I
VHW
,
TBVHW
8
VHW
2XWSXWYROWDJH
2XWSXWIUHTXHQF\
&XUUHQWVHWSRLQW,
TBVHW
U
U
U
U
0
Q
8
I
Figure14-79 Default setting of the U/f control after selecting Standard Drive Control
The Standard Drive Control mode has the following properties:
• At low speeds, a controlled motor current reduces the tendency of the motor to oscillate.
• With increasing speed, the converter changes from controlled motor current to U/f control
with load-dependent voltage boost.
• Selecting a technological application denes the characteristic:
I
VHW
8
VHW
I
VHW
,
TBVHW
,
TBVHW
0D[LPXPRXWSXW
YROWDJH
7HFKQRORJLFDODSSOLFDWLRQ
5DWHGPRWRUIUHTXHQF\
/LQHDU
3DUDEROLF
S
S
S
U
U
① A voltage boost optimizes open-loop speed control at low speeds
② The converter compensates the voltage drop across the stator resistance of the motor
Figure14-80 Characteristics after selecting Standard Drive Control
• Slip compensation is activated.
• Soft starting is not possible.
• Fewer setting options compared to U/f control
Functions
14.10Closed-loop drive control
SINAMICS G220 converter
466 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB