4.14.10 Maximum permissible signal cable lengths, converter in degree of
protection IP55
Technical data
Table 4-6 Maximum permissible signal cable lengths, IP55
Connection at the converter Cable length
24 V supply (terminals X124:1…
4)
If conducted disturbances occur on the 24V cable, we recommend
using a Schurter FPBB 3-103-715 line lter
Digital input
Failsafe digital input
Digital output DO0
Relay output DO1, DO2
Failsafe digital output
The maximum permissible connecting cable length is 1000m.
Temperature sensor The maximum permissible connection cable length is 300m.
Analog input
Analog output
10 V output voltage
The maximum permissible connection cable length is 30m.
24 V output voltage The maximum permissible connecting cable length is 1000m.
Fieldbus The maximum permissible connection cable length is 100m.
DRIVE-CLiQ The maximum permissible connection cable length is 100m.
4.14.11 Maximum permissible signal cable lengths, option module OM-SMT
Requirement
Only cables with an insulation that is designed for an ambient temperature of 75°C are
permissible.
Technical data
Sensor cable Cable length (copper cable) Cable cross-section
Without short-circuit detection ≤500m 0.5mm² / AWG 21
≤ 1500 m
1)
1.5mm² / AWG 16
≤ 2500 m
1)
2.5mm² / AWG 14
With short-circuit detection ≤50m 0.5mm² / AWG 21
≤150m 1.5mm² / AWG 16
≤250m 2.5mm² / AWG 14
1)
≤ 1 000 m for the temperature monitoring of explosion-protected motors, i.e. to comply with guideline
2014/34/EU (ATEX) or regulation 2016 No. 1107 (UKEX)
Application planning
4.14EMC-compliant installation
SINAMICS G220 converter
90 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB