14.10 Closed-loop drive control
14.10.1 Motor reactor, sine-wave lter, and cable resistance
Overview
The following components between the converter and the motor inuence the closed-loop
control quality of the converter:
• Motor reactors or sine-wave lters
• Motor cable with unusually high cable resistance
Description
In the factory setting, for the motor data identication, the converter assumes that neither a
motor reactor nor a sine-wave lter are connected at the converter output.
For the motor data identication, the converter assumes a cable resistance = 20% of the
stator resistance of the cold motor.
Correct parameter setting of the components between the converter and the motor improves
the closed-loop control quality of the motor.
Motor data identication is necessary after changing a parameter.
Parameters
The following list contains the parameters of the "Motor control" function.
Number Name Unit
p0230 Drive lter type motor side
p0233 Power unit motor reactor [mH]
p0234 Power unit sine-wave lter capacitance [µF]
p0235 Motor reactor in series number
p0352[0...n] Cable resistance [ohm]
14.10.2 Standard Drive Control operating mode
14.10.2.1 Standard Drive Control
Overview
Standard Drive Control is an open-loop speed control in which the converter sets the output
voltage using a U/f characteristic.
Functions
14.10Closed-loop drive control
SINAMICS G220 converter