EasyManua.ls Logo

Siemens SINAMICS G220 - Efficiency Optimization as a Function of the Motor Operating Point

Siemens SINAMICS G220
834 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Number Name Unit
r0333[0...n] Rated motor torque [Nm]
p0341[0...n] Motor moment of inertia [kgm²]
p0342[0...n] Ratio between the total and motor moment of inertia
p1226[0...n] Threshold for zero speed detection [rpm]
p1400[0...n].0...31 Speed control con󹪝guration
r1407.0...31 Status word speed controller
r1493 Moment of inertia total, scaled [kgm²]
p1496[0...n] Acceleration precontrol scaling [%]
p1498[0...n] Load moment of inertia [kgm²]
c1502[0...n] Freeze moment of inertia estimator
p1560[0...n] Moment of inertia estimator accelerating torque threshold
value
[%]
p1561[0...n] Moment of inertia estimator change time moment of inertia [ms]
p1562[0...n] Moment of inertia estimator change time load [ms]
p1755[0...n] Motor model changeover speed encoderless operation [rpm]
p5310[0...n].0...1 Moment of inertia precontrol con󹪝guration
r5311[0...n].0...5 Moment of inertia precontrol status word
p5312[0...n] Moment of inertia precontrol linear positive [s²]
p5313[0...n] Moment of inertia precontrol constant positive [kgm²]
p5314[0...n] Moment of inertia precontrol linear negative [s²]
p5315[0...n] Moment of inertia precontrol constant negative [kgm²]
14.10.10 E󹪟ciency optimization as a function of the motor operating point
Overview
The e󹪟ciency optimization optimizes the 󹪞ux of the motor depending on the operating point of
the motor. This has the following advantages:
Lower energy costs
Lower motor temperature rise
Lower motor noise levels
Requirement
The converter operates an induction motor.
The speed control is active.
Description of function
E󹪟ciency optimization is deactivated in the converter factory setting (p1401.14 = 0 signal).
The e󹪟ciency of an induction motor is determined by speed, torque and 󹪞ux. The torque and
speed are determined by the driven machine. E󹪟ciency optimization therefore uses the 󹪞ux
as the variable quantity.
Functions
14.10Closed-loop drive control
SINAMICS G220 converter
560 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB