The moment of inertia J of the motor and load is then obtained from the accelerating torque
M
B
and angular acceleration α (α=rate at which the speed changes):
J=M
B
/α
If all of the following conditions are met, the converter calculates the moment of inertia:
The measured accelerating torque M
B
must satisfy the following two conditions:
The sign of M
B
is the same as the direction of the actual acceleration
M
B
> p1560× rated motor torque (r0333)
Speed > p1755
The converter has calculated the load torque in at least one direction of rotation.
Acceleration setpoint > 81/s
2
(≙ speed change 480rpm per s)
The converter calculates the load torque again after acceleration.
Moment of inertia precontrol
In applications where the motor predominantly runs at constant speed, the converter can
rarely calculate the moment of inertia using the function described above. Moment of inertia
precontrol is available for situations such as these. The moment of inertia precontrol assumes
that there is an approximately linear relationship between the moment of inertia and the
load torque.
Example: For a horizontal conveyor, in a 󹪝rst approximation, the moment of inertia depends
on the load.
/RDGWRUTXH0/
0RPHQWRILQHUWLD-
Figure14-157 Moment of inertia precontrol
The relationship between load torque and torque is stored as a linear characteristic in the
converter.
In positive direction of rotation:
Moment of inertiaJ = p5312 × load torqueM
L
+ p5313
In negative direction of rotation:
Moment of inertiaJ = p5314 × load torqueM
L
+ p5315
You have the following options to determine the characteristic:
You already know the characteristic from other measurements. In this case, you must set the
parameters to the known values when commissioning the system.
The converter iteratively determines the characteristic by performing measurements during
motor operation.
Parameters
The following list contains the parameters of the "Moment of inertia estimator" function.
Functions
14.10Closed-loop drive control
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 559