14.10.4.3 Vdc_min controller (Vdc_min control)
Overview
The Vdc_min controller (kinetic bu󹪜ering) increases the drive availability because the kinetic
energy of the load accommodates brief power dips or failures.
Requirement
Requirements:
The driven load has a su󹪟ciently high inertia.
The application allows braking of the motor during a power failure.
Description of function
When the power dips or fails, the DC link voltage in the converter decreases. The Vdc_min
controller intervenes starting from an adjustable threshold. With kinetic bu󹪜ering active, the
converter covers its power loss and the losses in the motor with the kinetic energy of the load.
The speed of the load decreases but the DC link voltage remains constant with the Vdc_min
controller active. After the line supply returns, the converter resumes normal operation.
The Vdc_min controller can typically accommodate power failures of up to 1 second.
1PXFSGBJMVSF
7ED@NJODPOUSPMMFSJTBDUJWF
4QFFE
%$MJOLWPMUBHF
4XJUDIPOMFWFM
4QFFEUISFTIPME
(FOFSBUJOHPQFSBUJPO
U
U
Figure14-109 Principal mode of operation of the Vdc_min controller
Parameters
The following list contains the parameters of the "Vdc_min controller" function for U/f control.
Number Name Unit
r0056.0...15 Status word, closed-loop control
p0210 Device supply voltage [V]
p1280[0...n] Vdc controller or Vdc monitoring con󹪝guration (U/f)
Functions
14.10Closed-loop drive control
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 499