Table 7-19 Line supply cable connection without repair switch (line voltage 3AC 380...415 / 3AC440...500V, IP 55)
Converter
6SL4113-..□□-..F0
Line supply cable
-..□□- Frame
size
Rated power
in kW
Conductor cross-
section in mm²
(AWG)
Tightening torque in
Nm (lbfin)
Stripped
length inmm
(in)
Connection type
08…16 B 1.1 … 7.5 1.5 … 6 (15...9) 1.2 (10.6) 12 (0.5) Screw terminal
17 ...18 C 11 ... 15 2.5 … 16 (13...5) 2.5 … 3.4 (22.1 ... 30.1) 14 (0.6) Screw terminal
20...21 D1 18.5...22 16 … 35 (5 … 2) 5.6 (49.6) 25 (1) Screw terminal
23...24 D2 30...37 16 … 50(5… 1/0) 5.6(49.6) 25 (1) Screw terminal
26 ...27 E 45...55 35 … 70
1)
(2...2/0)
35 ...95
2)
(2...3/0)
10.2 (90.3) 30 (1.2) Screw terminal
1)
Line supply cable, nely stranded with end sleeve
2)
Line supply cable, solid conductor
Table 7-20 Line supply cable connection with repair switch (line voltage 3AC 380...415 / 3AC440...500V, IP 55)
Converter
6SL4113-..□□-..F0
Line supply cable
-..□□- Frame
size
Rated power
in kW
Conductor cross-
section in mm²
(AWG)
Tightening torque in
Nm (lbfin)
Stripped
length in mm
(in)
Connection type
08…16 B 1.1 … 7.5 2.5 … 6(13 …9) 2.0 ... 2.5 (17.7 ... 22.1) 9.5 (0.4) Screw terminal
17 ...18 C 11 ... 15 2.5 … 16
)
(13...5) 2.0 ... 2.5 (17.7 ... 22.1) 14 (0.6) Screw terminal
20...21 D1 18.5...22 6 … 16
1)
(9...5)
6 … 35
2)
(9...2)
2.5...3 (22.1...26.6) 14 (0.6) Screw terminal
23...24 D2 30...37 10 … 35
1)
(7...2)
10 ...50
2)
(7...1/0)
2.5...3 (22.1...26.6) 14 (0.6) Screw terminal
26 ...27 E 45...55 35 … 95 (2...3/0) 9.5...10 (84.1...88.5) 15 (0.6) Screw terminal
1)
Line supply cable, nely stranded with end sleeve
2)
Line supply cable, solid conductor
Table 7-21 Protective conductor connection at terminal X1 (line voltage 3AC 380...415 / 3AC440...500V, IP 55)
Converter
6SL4113-..□□-..F0
Protective conductor connection in terminal X1
-..□□- Frame
size
Rated power in
kW
Conductor cross-sec‐
tion in mm² (AWG)
Tightening torque in
Nm (lbfin)
Connection type
08…16 B 1.1 … 7.5 1.5 … 6(15 …9) 1.5 … 1.7
(13.3...15.0)
M5, screw terminal, outside
17 ...18 C 11 ... 15 1.5 … 16(15 …5) 1.5 … 1.7
(13.3...15.0)
M4, screw terminal, outside
20...21 D1 18.5...22 2.5 … 50 (13...1/0) 3.5 ... 4 (31.0 ... 35.4) M8, screw terminal, outside
Connecting
7.1Line system, motor and braking resistor
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 165