1&
Protective conductor of the power supply cord
Protective conductor of the converter power supply cord
Protective conductor between PE and control cabinet
Protective conductor of the motor connection cable
The minimum cross-section of the protective conductors depends on the cross-
section of the power supply or motor connection cable:
Power supply or motor connection cable ≤ 16mm
2
Minimum cross-section of the protective conductor = cross-section of the power supply or
motor connection cable
16mm² < power supply or motor connection cable ≤ 35mm
2
⇒ Minimum cross-section of the protective conductor = 16mm
2
Power supply or motor connection cable > 35mm
2
Minimum cross-section of the protective conductor = ½ cross-section of the power supply
or motor connection cable
Application planning
4.4Requirements for the protective conductor, converter in degree of protection IP20
SINAMICS G220 converter
66 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB