Description of function
A Modbus TCP register comprises 16bits. The values of the converter display parameters (r
parameters) cannot always be represented with 16 bits. In these particular cases, the maximum
value that can be represented is displayed.
Unsigned: 65535
Signed min: -32768
Signed max: 32767
Table 14-19 Control parameters with up to ten process data items
1)
Register Description Access
2)
Unit Scaling Value range Parameters
40100 Control word (see function diagram
2442)
R/W 1 r2050[0]
40101 Main setpoint R/W - 1 r2050[1]
40102 Control word 3 R/W - 1 r2050[2]
40103 Control word 4 R/W - 1 r2050[3]
40104 Process data item 5 R/W - 1 r2050[4]
40105 Process data item 6 R/W - 1 r2050[5]
40106 Process data item 7 R/W - 1 r2050[6]
40107 Process data item 8 R/W - 1 r2050[7]
40108 Process data item 9 R/W - 1 r2050[8]
40109 Process data item 10 R/W - 1 r2050[9]
1)
We recommend using registers 40150 … 40169. Registers 40100 … 40109 are compatible with converters that have
󹪝rmware < V6.1.
2)
"R" stands for read (with FC03), "W" for write (with FC06 or FC16) and "R/W" for read/write
Table 14-20 Control parameters with more than ten process data items
1)
Register Description Access
2)
Unit Scaling Value range Parameters
40150 Control word (see function diagram
2442)
R/W 1 r2050[0]
40151 Main setpoint R/W - 1 r2050[1]
40152 Control word 3 R/W - 1 r2050[2]
40153 Control word 4 R/W - 1 r2050[3]
40154 Process data item 5 R/W - 1 r2050[4]
40155 Process data item 6 R/W - 1 r2050[5]
40156 Process data item 7 R/W - 1 r2050[6]
40157 Process data item 8 R/W - 1 r2050[7]
40158 Process data item 9 R/W - 1 r2050[8]
40159 Process data item 10 R/W - 1 r2050[9]
40160 Process data item 11 R/W - 1 r2050[10]
40161 Process data item 12 R/W - 1 r2050[11]
40162 Process data item 13 R/W - 1 r2050[12]
40163 Process data item 14 R/W - 1 r2050[13]
Functions
14.5Modbus TCP communication
SINAMICS G220 converter
386 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB