Register Description Access
2)
Unit Scaling Value range Parameters
40164 Process data item 15 R/W - 1 ‑ r2050[14]
40165 Process data item 16 R/W - 1 ‑ r2050[15]
40166 Process data item 17 R/W - 1 ‑ r2050[16]
40167 Process data item 18 R/W - 1 ‑ r2050[17]
40168 Process data item 19 R/W - 1 ‑ r2050[18]
40169 Process data item 20 R/W - 1 ‑ r2050[19]
1)
Registers 40150 … 40159 are identical to registers 40100 … 40109.
2)
"R" stands for read (with FC03), "W" for write (with FC06 or FC16) and "R/W" for read/write
Table 14-21 Status data
Register Description Access
1)
Unit Scaling Value range Parameters
40110 Condition word (see function diagram
2452)
R - 1 ‑ c2051[0]
40111 Main actual value R - 1 ‑ c2051[1]
40112 Process data item 3 R - 1 ‑ c2051[2]
40113 Process data item 4 R - 1 ‑ c2051[3]
40114 Process data item 5 R - 1 ‑ c2051[4]
40115 Process data item 6 R - 1 ‑ c2051[5]
40116 Process data item 7 R - 1 ‑ c2051[6]
40117 Process data item 8 R - 1 ‑ c2051[7]
40118 Process data item 9 R - 1 ‑ c2051[8]
40119 Process data item 10 R - 1 ‑ c2051[9]
40120 Process data item 11 R - 1 ‑ c2051[10]
40121 Process data item 12 R - 1 ‑ c2051[11]
40122 Process data item 13 R - 1 ‑ c2051[12]
40123 Process data item 14 R - 1 ‑ c2051[13]
40124 Process data item 15 R - 1 ‑ c2051[14]
40125 Process data item 16 R - 1 ‑ c2051[15]
40126 Process data item 17 R - 1 ‑ c2051[16]
40127 Process data item 18 R - 1 ‑ c2051[17]
40128 Process data item 19 R - 1 ‑ c2051[18]
40129 Process data item 20 R - 1 ‑ c2051[19]
1)
"R" stands for read (with FC03), "W" for write (with FC06 or FC16) and "R/W" for read/write
Table 14-22 Inputs and outputs
Register Description Access
1)
Unit Scaling Value range Parameters
40200 Digital output DO0 R/W - - - r0747.0, c0730
2)
40201 Digital output DO1 R/W - - - r0474.1, c0731
2)
40202 Digital output DO2 R/W - - - r0747.2, c0732
2)
40240 Digital input DI0 R - - - r0722.0
Functions
14.5Modbus TCP communication
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 387