Register Description Access
1)
Unit Scaling Value range Parameters
40402 Failure number, index 2 R - 1 0 … 65535 r0947 [2]
40403 Fault number, index 3 R - 1 0 … 65535 r0947 [3]
40404 Fault number, index 4 R - 1 0 … 65535 r0947 [4]
40405 Fault number, index 5 R - 1 0 … 65535 r0947 [5]
40406 Fault number, index 6 R - 1 0 … 65535 r0947 [6]
40407 Fault number, index 7 R - 1 0 … 65535 r0947 [7]
40408 Alarm number R - 1 0 … 65535 r2122 [0]
40409 Actual alarm code R - 1 0 … 65535 r2132
40420 Safety Integrated alarm number R - 1 0 … 65535 r60047[0]
40421 Safety Integrated alarm number R - 1 0 … 65535 r60047[1]
40422 Safety Integrated alarm number R - 1 0 … 65535 r60047[2]
40423 Safety Integrated alarm number R - 1 0 … 65535 r60047[3]
40424 Safety Integrated alarm number R - 1 0 … 65535 r60047[4]
40425 Safety Integrated alarm number R - 1 0 … 65535 r60047[5]
40426 Safety Integrated alarm number R - 1 0 … 65535 r60047[6]
40427 Safety Integrated alarm number R - 1 0 … 65535 r60047[7]
40499 PRM ERROR code R - 1 0 … 255 -
1)
"R" stands for read (with FC03), "W" for write (with FC06 or FC16) and "R/W" for read/write
Table 14-25 Technology controller
Register Description Access
1)
Unit Scaling Value range Parameters
40500 Technology controller enable R/W - 1 0…1 c2200, r2349.0
40501 Technology controller MOP R/W % 100 -200.0 … 200.0 p2240
40510 Time constant for actual value lters of
the technology controller
R/W - 100 0.00 … 60.0 p2265
40511 Scaling factor for actual value of the tech‐
nology controller
R/W % 100 0.00 … 500.00 p2269
40512 Proportional gain of the technology con‐
troller
R/W - 1000 0.000 … 65.535 p2280
40513 Integral time of the technology controller R/W s 1 0 … 60 p2285
40514 Time constant D-component of the tech‐
nology controller
R/W - 1 0 … 60 p2274
40515 Max. limit of technology controller R/W % 100 -200.0 … 200.0 p2291
40516 Min. limit technology controller R/W % 100 -200.0 … 200.0 p2292
40520 Eective setpoint acc. to internal technol‐
ogy controller MOP ramp-function gen‐
erator
R % 100 -100.0 … 100.0 r2250
40521 Actual value of technology controller af‐
ter lter
R % 100 -100.0 … 100.0 r2266
40522 Output signal technology controller R % 100 -100.0 … 100.0 r2294
2)
"R" stands for read (with FC03), "W" for write (with FC06 or FC16) and "R/W" for read/write