Table 17-8 Power and currents
Property Unit Article number: 6SL4112-...☐☐-..F0
15 16 17 18 20 21 23
Rated power at 230V With low
overload
kW 5.5 7.5 11 15 18.5 22.0 30.0
With high
overload
kW 4.0 5.5 7.5 11.0 15.0 18.5 22.0
Rated power at 240V With low
overload
hp 7.5 10.0 15.0 20.0 25.0 30.0 40.0
With high
overload
hp 5.0 7.5 10.0 15.0 20.0 25.0 30.0
Input current at 230V With low
overload
A 21.7 29.5 41.8 53.9 66.5 76.0 103.2
With high
overload
A 16.8 25.8 39.9 43.1 61.3 69.5 91.0
Output current at 230V Without
overload
A 27.7 34.9 47.2 64.7 77.0 92.4 114.9
With low
overload
A 27.0 34.0 46.0 63.0 75.0 90.0 112.0
With high
overload
A 19.0 27.0 40.0 46.0 63.0 75.0 90.0
Input current at 240V With low
overload
A 20.1 26.6 39.5 49.7 62.5 72.1 96.1
With high
overload
A 15.3 22.9 29.0 42.4 54.4 67.3 81.1
Output current at 240V Without
overload
A 22.6 28.8 43.1 55.4 69.8 82.1 106.7
With low
overload
A 22.0 28.0 42.0 54.0 68.0 80.0 104.0
With high
overload
A 15.2 22.0 28.0 42.0 54.0 68.0 80.0
Technical data
17.3Power, input current, output current
SINAMICS G220 converter