Converter
6SL4113-..□□-..F0
Connection at the converter for the motor
-..□□- Frame
size
Rated power
in kW
Conductor cross-
section in mm²
(AWG)
Tightening torque in
Nm (lbfin)
Stripped
length in mm
(in)
Connection type
23...24 D2 30...37 10 … 50(7… 1/0) 5 … 6(44.3 …53.1) 19 (0.7) Screw terminal
26 ...27 E 45...55 35 … 95(2… 3/0) 10 … 12 (88.5 … 106.2) 25 (1) Screw terminal
Table 7-8 Line supply cable connection (line voltage 3AC 380...415 / 3AC440...500V, IP 20)
Converter
6SL4113-..□□-..F0
Line supply cable
-..□□- Frame
size
Rated power
in kW
Conductor cross-
section in mm²
(AWG)
Tightening torque in
Nm (lbfin)
Stripped
length in mm
(in)
Connection type
08 ... 13 A 1.1... 4 1.5 … 4(15 …11) 0.4 … 0.5 (3.5 … 4.4) 7 (0.3) Screw terminal
15 ... 16 B 5.5 … 7.5 4 … 6(11 …9) 0.5 … 0.6 (4.4 … 5.3) 12 (0.5) Screw terminal
17 ...18 C 11 ... 15 6 … 16(9 …5) 1.2 … 2(5.3 …17.7) 10 (0.4) Screw terminal
20...21 D1 18.5...22 6 … 35 (9 … 2) 3.8 … 4(33.6 …39.8) 18 (0.7) Screw terminal
23...24 D2 30...37 10 … 50(7… 1/0) 5 … 6(44.3 …53.1) 19 (0.7) Screw terminal
26 ...27 E 45...55 35 … 95(2… 3/0) 10 … 12 (88.5 … 106.2) 25 (1) Screw terminal
Table 7-9 Protective conductor connection in terminal X1 (line voltage 3AC 380...415 / 3AC440...500V, IP 20)
Converter
6SL4113-..□□-..F0
Protective conductor connection in terminal X1
-..□□- Frame
size
Rated power in
kW
Conductor cross-sec‐
tion in mm² (AWG)
Tightening torque in
Nm (lbfin)
Connection type
08 ... 13 A 1.1... 4 1.5 … 4(15 …11) 2 … 3(17.7 …26.6) M4, screw terminal, outside
15 ... 16 B 5.5 … 7.5 1.5 … 6(15 …9) 2 … 3(17.7 …26.6) M4, screw terminal, outside
17 ...18 C 11 ... 15 1.5 … 16(15 …5) 2 … 3(17.7 …26.6) M4, screw terminal, outside
20...21 D1 18.5...22 1.5 … 35(15 …2) 4 … 5(35.4 …44.3) M5, screw terminal, outside
23...24 D2 30...37 1.5 … 50(15… 1/0) 4 … 5(35.4 …44.3) M5, screw terminal, outside
26 ...27 E 45...55 2.5 … 95(13… 3/0) 4 … 5(35.4 …44.3) M5, screw terminal, outside
Table 7-10 Protective conductor connection in terminal X2 (line voltage 3AC 380...415 / 3AC440...500V, IP 20)
Converter
6SL4113-..□□-..F0
Protective conductor connection in terminal X2
-..□□- Frame
size
Rated power in
kW
Conductor cross-sec‐
tion in mm² (AWG)
Tightening torque in
Nm (lbfin)
Connection type
08 ... 13 A 1.1... 4 1.5 … 4(15 …11) 2 … 3(17.7 …26.6) M4, screw terminal, outside
15 ... 16 B 5.5 … 7.5 1.5 … 6(15 …9) 2 … 3(17.7 …26.6) M4, screw terminal, outside
17 ...18 C 11 ... 15 1.5 … 16(15 …5) 2 … 3(17.7 …26.6) M4, screw terminal, outside
Connecting
7.1Line system, motor and braking resistor
SINAMICS G220 converter
156 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB