Description of function
The following residual-current devices are available, depending on the converter:
RCD for converters with rated input currents ≤80A based on LO:
Siemens SIQUENCE RCCB (series 5SV364.-4), type B, short-time delayed [K], with a rated
residual current of 300mA.
The RCCB is connected in series with the overcurrent protection devices.
RCD for converters with rated input currents ≤ 160A based on LO:
Residual-current device RCD520B from Siemens (3VA9113-0RL21) mounted on a Siemens
molded-case circuit breaker (series 3VA1).
Recommended settings:
Response characteristic B
Residual current trip level 300mA
Response delay≥0.06s
RCD for converters with rated input currents > 160A based on LO:
Modular residual-current device from Siemens (MRCD, type B, 5SV8111-4KK) with current
transformer (5SV870.-2K), circuit breaker (series 3VA1) and trip unit (3VA9988-0BL30).
0RGXODUUHVLGXDO
FXUUHQWSURWHFWLYH
GHYLFH05&'
0HDVXULQJFXUUHQW
WUDQVIRUPHU
&LUFXLWEUHDNHU
9$
7ULSHOHPHQW
&LUFXLWEUHDNHU
59
2WKHUb9ORDGV
7RWKHFRQYHUWHU
,! ,!,!
/
3(
/
/
,! ,!,!
8
$
//
/
$


6,723$
Figure7-12 Modular residual-current device
Connecting
7.1Line system, motor and braking resistor
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 175