Error
value1
Meaning
14 hex Inadmissible value (change request with a value that is within the limits but which is illegal for other permanent
reasons, i.e. a parameter with dened individual values)
15 hex Response too long (the length of the actual response exceeds the maximum transfer length)
16 hex Illegal parameter address (illegal or unsupported value for attribute, number of elements, parameter number,
subindex or a combination of these)
17 hex Illegal format (change request for an illegal or unsupported format)
18 hex Number of values not consistent (number of values of the parameter data to not match the number of elements in
the parameter address)
19 hex Drive object does not exist (access to a drive object that does not exist)
20 hex Parameter text cannot be changed
21 hex Service is not supported (illegal or not support request ID).
6B hex A change request for a controller that has been enabled is not possible. (The converter rejects the change request
because the motor is switched on. Observe the "Can be changed" parameter attribute in the parameter list.)
6C hex Unknown unit.
6E hex Change request is only possible in the "Motor commissioning" state.
6F hex Change request is only possible in the "Power unit commissioning" state.
70 hex Change request is only possible in the "Quick commissioning" ("Basic commissioning") state.
71 hex Change request is only possible if the converter is ready.
72 hex Change request is only possible for a parameter reset (restore factory settings).
73 hex Change request is only possible in the "Safety Integrated commissioning" state.
74 hex Change request is only possible in the "Commissioning the technological application/units" state
75 hex Change request is only possible in a commissioning state.
76 hex Change request is not possible for internal reasons.
77 hex Change request is not possible during download.
81 hex Change request is not possible during download.
82 hex Accepting the master control is inhibited.
83 hex Desired interconnection is not possible (signal source does not supply oat value, but the signal sink requires oat)
84 hex Converter does not accept a change request (converter is busy with internal calculations)
85 hex No access methods dened.
86 hex Write access only during commissioning of the data records (the operating status of the converter prevents a
parameter change)
87 hex Know-how protection active: access inhibited
88hex Write access only in the commissioning state Safety Integrated device
89hex Access blocked due to missing UMAC function right
C8hex Change request below the currently valid limit (change request for a value that lies within the "absolute" limits, but
is below the currently valid lower limit)
C9hex Change request above the currently valid limit (example: a parameter value is too large for the converter power)
CC hex Change request not permitted (change is not permitted as the access code is not available)