Table 14-65 Signal interconnection of the inputs and outputs
Input Signal interconnection Output Signal interconnection
DI0
DI1
DI2
c0840[0] = r0722.0
c1113[0]=r0722.1
c2103[0]=r0722.2
DO0
DO1
c0730 = r0052.3
c0731 = r0052.2
AI 0 c1070[0] = r0755[0] AO 0 c0771[0] = r0021
Parameters
The following list contains the parameters of function "I/O presetting Standard I/O with analog
setpoint".
Number Name Unit
r0722.0...22 Digital inputs status
c0730 Signal for terminal DO 0
c0731 Signal for terminal DO 1
r0755[0...1] Analog inputs, actual value in percent [%]
c0771[0] Analog output signal
c0840[0...n] ON / OFF (OFF1)
c1070[0...n] Main setpoint
c1113[0...n] Setpoint inversion
c2103[0...n] 1st acknowledge faults
Functions
14.8Inputs/outputs
SINAMICS G220 converter
422 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB