- 2251 -
1
Input/output terminals
Analog inputs 0 ... 1 (AI 0 ... AI 1)
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
<1>
x
2
x
1
x
1
· x
2
100 %
p2000 … r2004
–
+
AI 0–
AI 1–
AI 0+
AI 1+
A
D
<2> <3>
1
0
1
0
<2>
<4>
20 mA
20 mA
Analog inputs simulation mode setpoint
-20.000 ... 20.000
p0798[0..1] (0.000)
Analog inputs simulation
mode
0 ... 1
p0797[0..1] (0)
r0752[0..1]
Analog inputs actual input voltage/current
Analog inputs offset
-20.000 ... 20.000
p0763[0..1] (0.000)
+
+
x
1
y
2
x
2
y
1
y
x
[%]
[%]
Analog inputs type
0 ... 4
p0756[0..1] (4)
Analog inputs
characteristic value x1
-50.000 ... 160.000
p0757[0..1] (0.000)
Analog inputs
characteristic value x2
-50.000 ... 160.000
p0759[0..1] (10.000)
Analog inputs characteristic value y2
-1000.00 ... 1000.00 [%]
p0760[0..1] (100.00)
Analog inputs characteristic value y1
-1000.00 ... 1000.00 [%]
p0758[0..1] (0.00)
yx
0 %
0
1
-1
0
1
0
1
<1>
4
1
0, 2
4 mA
0
T 0
2 V
3
100 μs
r0751.0..9
Analog inputs
status word
F03505 "Analog input
wire breakage"
c0767[0..1]
(0)
Analog inputs
inversion
Analog inputs smoothing
time constant
0.0 ... 1000.0 [ms]
p0753[0..1] (0.0)
Analog inputs noise
suppression window
0.00 ... 20.00 [%]
p0768[0..1] (0.00)
c0769[0..1]
(1)
Analog inputs enable
r0755[0..1]
Analog inputs,
actual value in
percent [%]
Analog inputs activate
absolute value generation
p0766[0..1] (0)
Analog inputs wire-break monitoring delay
time
0 ... 1000 [ms]
p0762[0..1] (100)
y = x if
|y - x| > p0768
otherwise y = y(old)
Analog inputs wire break monitoring, response threshold
0.00 ... 20.00
p0761[0..1] (2.00)
Reference quantities, e. g.
Sampling time of the analog inputs: p0799[1] (4 ms)
Differential input!
The maximum voltage difference between analog input terminals AI+, AI-, and the ground must not exceed 35 V.
For current measurement (p0756[0...1] = 2, 3), the voltage between differential inputs AI+ and AI- must not exceed
10 V or the impressed current must not exceed 80 mA, as otherwise the input will be damaged.
For p0756[0...1] = 0, 1, 4 the unit is V.
For p0756[0...1] = 2, 3 the unit is mA.
Possible settings p0756[0...1]:
0: Unipolar voltage input (0 V ... +10 V)
1: Unipolar voltage input monitored (+2 V ... +10 V)
2: Unipolar current input (0 mA ... +20 mA)
3: Unipolar current input monitored (+4 mA to +20 mA)
4: Bipolar voltage input (-10 V ... +10 V)
Wire breakage sensing only activated when p0756 = 1, 3.
<3>
<2>
<4>
+
1,3
≠1,3
<2>
<2>
Analog inputs dead zone
0.000 ... 20.000
p0764[0..1] (0.000)
<2> <2>
Figure14-37 2251 - Analog inputs 0 … 1 (AI 0 … AI 1)
Functions
14.8Inputs/outputs
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 427